Product Details
|
Product Group:
power cable
Product Description
Rubber cable HO5RR-F:
Reference standard: DIN VDE 0282
Applicable scope: Rated voltage 300/500V or below. Applied in electrical appliance, electromotive tools
Cable characteristic:
Cable working temperature should not exceed 65º C
- Cable have a certain extent of temperature resistance and oil resistance, fit to work outside and work in the smeary environment.
- Reach standard GB/T 18380.1-2001 vertical flame test.
- When cable in temperature of 20º C the insulation resistance between conductors above 50M¦¸. Km.
Structure data and primary capability:
Specification Conductor Normal thickness of insulation mm Normal thickness of jacket mm Over diameter mm "Max conductor resistance at 20º C ¡Ü¦¸/km
" Ampere rating A
No. Of core normal cross-sectional area of conductor mm2 No. / Dia. Mm
2 0.75 24/0.2 0.6 0.8 6.1— 7.0 26 14
1.00 32/0.2 0.6 0.9 6.6— 7.3 19.5 17
1.50 30/0.25 0.8 1.0 8.1— 9.1 13.3 21
2.50 49/0.25 0.9 1.1 9.7— 11.0 7.98 30
3 0.75 24/0.2 0.6 0.9 6.7— 7.6 26 12
1.00 32/0.2 0.6 0.9 7.0— 7.9 19.5 14
1.50 32/0.25 0.8 1.0 8.6— 9.6 13.3 18
2.50 49/0.25 0.9 1.1 10.1— 11.8 7.98 25
4.00 56/0.30 1.0 1.2 12.4— 14.3 4.95 35
6.00 84/0.30 1.0 1.3 14.1— 16.0 3.3 45
4 0.75 24/0.2 0.6 0.9 7.3— 8.2 26 11
1.00 32/0.2 0.6 0.9 7.6— 8.5 19.5 13
1.50 32/0.25 0.8 1.1 9.6— 10.9 13.3 18
2.50 49/0.25 0.9 1.2 11.5— 13.2 7.98 25
4.00 56/0.30 1.0 1.3 13.9— 15.8 4.95 36
6.00 84/0.30 1.0 1.4 15.7— 17.6 3.3 45
5 0.75 24/0.2 0.6 1.0 8.1— 9.1 26 11
1.00 32/0.2 0.6 1.0 8.5— 9.5 19.5 13
1.50 32/0.25 0.8 1.1 10.5— 12.0 13.3 18
2.50 49/0.25 0.9 1.3 12.8— 14.7 7.98 25
|