MIC Chinese Simplified Chinese Traditional English
Inquiry Basket Inquiry Basket (0) item | Recent Visit History | Join Audited Suppliers

Home » Product Directory » Electrical & Electronics » Power Supply & Distribution » UPS » Online UPS (Epower Series(10-200KVA))

Online UPS (Epower Series(10-200KVA))

Online UPS (Epower Series(10-200KVA))
Online UPS (Epower Series(10-200KVA))

Product Description

Epower(10~120KVA)
3: 3 phase

Application:
Small-medium computer data center, industrial process and other mission-critical equipment

Features:
1. Three phase in, three phase out
2. Double conversion on line technology
3. Static bypass
4. Manual maintenance bypass
5. Double CPU control
6. LCD with control panel
7. Remote management
8. Parallel redundant
9. Self diagnosis
10. Low noise
11. High efficiency cuts down your expense
12. Wide input voltage range

SeriesEpower Series
Capacity10KVA15KVA20KVA30KVA40KVA60KVA80KVA100KVA120KVA160KVA200KVA
Power8KW12KW16KW24KW32KW48KW64KW80KW96KW128KW160KW
Power Factor0.8
Input
Phase3 phase 4 wire and ground
Voltage Range+/-20%
Frequency Range45 – 65Hz
Rectifier3 phase 6 pulses
Output
Phase3 phase 4 wire and ground
Wave formSine wave
Crest Factor3:1
Rated voltage380/400/415V optional
Phase voltage setting200 - 244VAC   (control panel )
Transient response+/-5%, 10ms
Frequency50 / 60 Hz
Frequency stability+ / - 0.05%
Range of phase lockWith synchronization:    +/-0.05%. Without synchronization: + /- 2% (settable +/-1% on the control panel)
Total harmonic distortion3% ( linear load)
Short circuit currentShort current for 0.1s (200% current)
Overload capacity110% /125% /150% rated current 300 min/ 10min /1min
Battery
BatteryMaintenance free lead-acid cell
DC Voltage                                                 384VDC                                  432VDC480VDC
Bypass
TypeStatic state + manual maintenance bypass
Input Phase3 phase 4 wire and ground
Input voltage range15% - 25% (the front control panel selectable)
Input frequency range+/-1%   ~   +/- 5% the front control panel selectable
Transfer timeInverter / bypass transfer switch time(Overload): 0ms   inverter / bypass transfer switch time (fault inverter) 1ms
Overload capacity (10 min)170%180%170%170%170%140%130%125%125%125%125%
System
Remote signalingDry contact (battery low, battery discharging, bypass/ fault); output 12Vdc/80mA
Remote controlEPO and bypass
Communication interfaceRS232 ( SNMP , modem optional )
Running temperature0-40 degree Celsius
Relative HumidityLess than 95% (without condensing)
Altitude1000m output nominal power (with increase of 100m, it will reduce output of 1%) max 4000m
Noise at 1 Mless than 60 dB
Inverter Efficiency92%93%
Degree of protectionIP20
Applicable StandardsEN50091-1-EMC   EN50091-2liv.A
OptionalIsolating transformer
Harmonic wave suppression filter
Parallel modules can be up to six
Net/Gross   weight (Kg)223/280260/317260/317336/393351/408497/574556/633756/856901/10011300/14001350/1450
Unit Dimension(W×D×H) mm555×725×1220800×745×14001070×745×14001420×745×1810
Packing Dimension(W×D×H) mm660×855×1425880×945×15851254×875×15851520×880×2000

More Product Features

   
Trademark:  KSTAR
Model NO.:  Epower Series(10-200KVA)
Standard:  ISO9001, ISO14001
Company: Shenzhen Kstar Science-Technology Co., Ltd.

Click here to send inquiry