Application scope
It can protect the electric line equipment from overload and short circuit.
Technical parameter
Electric parameter:
Up to electrical standard: EN60898 GB10963 IEC898
Rated voltage(Ue): 230/400V; 50/60HZ
Rated breaking capacity:
10kA IEC898(0. 5-63A)
15kA IEC947-2(0. 5-63A)
DC short circuit breaking capacity: Max 48V(L7-10kA)single-pole
Max 250V(L7-DC, 6kA)single-pole
Characteristic curve B, C, D
Max connectable fuse: 100AgL(than 10kA)
Selectivity class: Class 3
Working ambient temperature: -5~+40OC
Enclosed protective class: IP40 (under mounting)
Service life: Electric no less than 8000 times make-break operation
Machinery no less than 20, 000 times make-break operation
Mechanical Parameter:
Exposed face length: 45mm
Casing height: 80mm
Casing width: 17. 5mm/pole(single-pole) 26. 3mm: 1P+N(1. 5 modules)
Installation mode: Adopting IEC standard guide rail 35mm
Terminal form: The double function terminal can connect with busbar and conductor.
Connecting capacity of terminal: Conductor 1-25mm2(excepted 1P+N)
1-25mm2/1-2 10mm2(N)(1P+N)
Busbar thickness: 0. 8-2mm