1. Introduction
The ASENWARE automatic extinguisher control panel is designed in accordance with European standards EN54-2 and EN54-4 Fire Detection and Fire Alarm systems - Control and Indicating Equipment and EN12094-1 Fixed firefighting systems - Components for gas extinguishing systems - Part 1: Requirements and test methods for electrical automatic control and delay devices.
The control equipment is a combined fire alarm control panel and extinguish ing system and has three detection zones, any or all of which are capable of contributing to the extinguishant release decision.
Control panels have an integral, mains powered battery charger and power supply designed in accordance with the requirements of EN54-4.
In addition to the requirements of EN54-2 the control panel has the following facilities:
Test condition to allow the automatic resetting of zones in alarm for testing purposes. EN54-2 Section 10 option with requirements
Delay of the actioning of fire alarm devices (sounders) so that an alarm may be verified before a premises is evacuated. EN54-2 Section 7.11 option with requirements.
Fire alarm devices to enable an audible warning to be sounded throughout premises upon the detection of a fire condition or the operation of a manual call point. EN54-2 Section 7.8 option with requirements
In addition to the requirements of EN54-2, all control panels have voltage free relay contacts for fire and local fire which operate upon a fire condition. These are to be used for local control and signaling.
In addition to the requirements of EN12094-1 the control panel has the following facilities:
Delay of extinguishing signal of up to 60 seconds. EN12094-1 Section 4.17 option with requirements.
Signal representing the flow of extinguishing agent to indicate the released condition. EN12094-1 Section 4.18 option with requirements.
Monitoring of the status of components by way of a low pressure switch input. EN12094-1 Section 4.19 option with requirements.
Emergency hold device to enable the extinguishant delay time to be extended. EN12094-1 Section 4.20 option with requirements.
Control of flooding time to deactivate the releasing output after a set period of time. EN12094-1 Section 4.21 option with requirements.
Manual only mode to disable the release of extinguishant via automatic detection devices. EN12094-1 Section 4.23 option with requirements.
Triggering of equipment outside the system by way of first and second stage contacts, extract fan output etc. EN12094-1 Section 4.26 option with requirements
Activation of alarm devices with different signals to indicate pre-discharge and released warnings using different sounds. EN12094-1 Section 4.30 option with requirements.
| ITEM | ELECTRICAL RATING | COMMENT |
| Mains supply | 90 to 270VAC, 50Hz/60Hz(100 Watts maximum) | |
| Mains supply fuse | 3 Amp ( F3A L250V) | Replace only with similar type |
| Power supply rating | 3 Amps total including battery charge 28V +/- 2V | |
| Maximum ripple current | 200 millivolts | |
| Battery type | Two 12 Volt sealed lead acid in series. | 7Ah maximum |
| Battery charge voltage | 27.6VDC nominal | |
| Battery charge current | 0.7A maximum | |
| Battery fuse | 20mm, 3.15 glass | |
| Current draw in mains fail condition | 0.095 Amps | With buzzer sounding |
| Current draw in second stage alarm | 0.235A | Two zones in fire(470 ohm in circuit) |
| Current draw in post discharge condition | 0.310A | solenoid outputs active |
| Maximum current draw from batteries | 3Amps | With main power disconnected |
| R0V output | Fused at 500Ma with electronic fuse | |
| Sounder outputs | 21 to 28V DC Fused at 500mA with electronic fuse | 1.6Amp total load over all circuits |
| Fault relay contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
| Fire relay contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
| Local fire relay contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
| First stage contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
| Second stage contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
| Extract contact rating | 5 to 30VDC 1A Amp maximum for each | Volt free changeover contact |
| Zone quiescent current | 0mA minimum, 2mA maximum | |
| Terminal capacity | 0.5mm 2 to 2.5mm 2 solid or stranded wire | |
| Number of detectors per zone | Dependent on type | |
| Number of sounders per circuit | Dependent on type and current consumption | |
| Detection circuit end of line | 6K8± 5% 1/2 Watt resistor | |
| Monitored input end of line | 6K8± 5% 1/2 Watt resistor | |
| Sounder circuit end of line | 10K± 5% 1/2 Watt resistor | |
| Extinguishant output end of line | 1N4004 Diode | |
| No. of detection circuits | Four 21 to 28V DC | |
| No. of sounder circuits | Three 21 to 28V DC | 2X first stage, 1 X second stage |
| Extinguishant release output | 21V to 28V DC. Maximum load 1 Amp | |
| Extinguishant release delay | Adjustable 0 to 75 seconds | 5 second steps |
| SIL, AL, FLT, RST inputs | Switched – ve, min resistance 0 ohms, max 470 ohms | |
| Zone normal threshold (Allowable EOL) | 10K ohms to 2K ohms | Use 6K8 end of line resistor |
| Detector alarm threshold | 1K ohms to 390 ohms | |
| Call point alarm threshold | 370 ohms to 150 ohms | |
| Short circuit threshold | 130 ohms to 0 ohms | |
| Head removal condition | 15.5 to 17.5 volts+/- 5% | |
| Cabling | FP200 or equivalent | Metal cable glands must be used. |
| Monitored inputs normal threshold | 10K ohms to 2K ohms | |
| (Allowable EOL) | ||
| Monitored inputs alarm threshold | 2K ohms to 150 ohms+/-5% | |
| Monitored inputs Short circuit threshold | 140 ohms to 0 ohms+/-5% | |
| Status unit/Ancillary board connection | Two wire RS485 connection with electronic fuse. | Max. of 16 units-RS485 data cable |
| Status unit power output | 21 to 28V DC, Fused at 500mA with electronic fuse. | 300 milliamp maximum load |
More Product Features
| Trademark: | ASENWARE |
|---|---|
| Model NO.: | AW-GEC2158 |
| Standard: | CE |
| Productivity: | 10000PCS/Year |
| Origin: | China |
| Packing: | Carton |
| Type: | Fire Extinguisher |
| Company: | Shenzhen Widesense Technology Co., Ltd. |
Most Popular
-

U. S Standard Hydrant
1) The ground fire hydrant is a fire water supply ... -

ABC/BC Fire Fighting Powder En 615 (Dry Powder)
ABC/BC Powder Purity 30-90%, EN 615 Approved ... -

1kg Powder Fire Extinguisher
1. Products: Abc/bc fire extinguisher 2. Types: ...
-

CO2 Valve (FY-22200)
We are specialized in producing CO2 valve, dry ... -

Fire Extinguisher Pressure Gauge/Extinguisher Gauge/ ...
Fire Extinguisher Pressure Gauge, Fire ... -

Tracked Fire Truck, Amphibious Fire Engine, Fire Fighting ...
Manufacturer of fire trucks, special vehicles, ...
-

PS Series Adjustable Fire Monitor
PS Series Adjustable Fire Monitor has ... -

Fire-Fighting Pump
Features: 1) Many kinds available 2) Wide ... -

Hfc-227ea Fire Suppression System FM200
1. THIS SYSTEM 3 PARTS: PART 1: FIRE ALARM & ...
-

Fire Extinguisher (MT02)
CO2 fire extinguisher, specification: 3KG, 4KG, ... -

Door-open Fire-resistant Cabinet (FRC-320)
Outside: (H)1280mm*(W)896*(D)560mm ... -

Isuzu Foam / Water Tank Fire Truck (SXF5220GXFPM100W / ...
ISUZU Foam Fire Vehicle/ISUZU Water Tank Fire ...
-

Fire Extinguisher Dry Power
Abc, Bc Dry Power For Fire Extinguisher -

Aluminum High Pressure Tank
Service pressure: 3000psi Burst pressure: 4500psi -

Fire Hose
Fire hose with dia from 1" to 6". With a working ...
Quick Products |
Inquiry Basket (