Asenware Conventional Fire Alarm Panel 4 Zone (AW-CFP2166-4)

Min. order: 1 Piece
Trade Terms: FOB
Payment Terms: L/C, T/T, D/P, Western Union, Paypal
Trademark: Asenware

Product Detail

Basic Info
  • Model NO.: AW-CFP2166-4
  • Export Markets: Global
Additional Info
  • Trademark: Asenware
  • Packing: Carton
  • Standard: EN54-2&4, CE
  • Origin: China
  • HS Code: 8531100000
  • Production Capacity: 100000PCS/Year
Product Description

1. AW-CFP2166 series conventional fire alarm panel is designed based on EN54 part 2&4 standard.
2. It is modularized design, the panel can extend from 1 zone to 32 zones easily.
3. It has 2 level control mode by a lock
4. It has 24VDC and 5VDC power supply output.
5. It has FIRE and FAULT signal output.
6. It has 2 general sounders output.
7. Each zone has 1 circuit detectors input.
8. Each zone can be disable by a button.
9. It has RESET button to reset the panel.
10. It has SILENCE button to stop BUZZER and SOUNDERS.
11. It has EVACUATE button to start a manual fire alarm immediately.
12. It has battery low protection function, when battery voltage lower than 21VDC, battery will be cut off automatically until the mains power is on.
13. It has an optional GSM module for fire alarm by SMS.
14. It is economic, user-friendly and easy maintenance.

ITEM 1Zone panel 2Zone panel 4-16 Zone panel 4-32 Zone panel
Photo        
Model No. AW-CFP2166-01 AW-CFP2166-02 AW-CFP2166-04-16 AW-CFP2166-04-32
Power specification  
Mains supply voltage 110VAC or 240VAC
Internal power supply 27.2VDC
Total output current limited 500mA @ 240VAC 500mA @ 240VAC 3A @ 240VAC 3A @ 240VAC
Main supply monitor for fault Yes
Battery protection for low voltage Yes
Batteries (default configuration) 12V2AH*2
Detector circuit specification  
Number of circuit 1 2 4-16 4-32
Line fault monitor for open circuit Yes
Line fault monitor for short circuit Yes
Line fault monitor for detector removal Yes, if End of Line Monitor Unit fitted in place of End of Line Resistor
End of Line device 6.8k Ω , 5% tolerance, 0.25W (colour code-blue, grey, red, gold)
Detector continuity diodes Silicon 1N4001 or Schottky type (required if End of Line Monitor Unit fitted to give Detector Removal Fault)
Call point resistor value 470 to 680 Ω , 0.225 or 0.5 watt
Maximum number of smoke/heat detectors per zone 20 (based on a total detector current of 2mA, each detector consuming 100μ A). Note: if End of Line Monitor Unit is fitted, for correct operation maxmum voltage drop must not exceed 12 volts.
Maximum number of manual call points per zone No limit
Sounder circuit specification  
Number of general circuits 2
End of line resistor value 6.8k Ω , 5% tolerance, 0.25W (colour code-blue, grey, red, gold)
Line fault monitor for open circuit Yes
Line fault monitor for short circuit Yes
Outputs fused AT 400mA
Maximum number of bells @ 20mA of each sounder output 20
Fuses  
Battery fuse 1.5A F 20mm
Sounder outputs 500mA F 20mm
Fire and fault output  
Output type NC and NO relay
Maximum current 100mA
Connection block  
Largest acceptable conductor size 2.5mm 2
Smallest acceptable conductor size 0.75mm 2
Size and weight    
Dimensions(mm) 272*200*70mm 320*231*90mm 395X502X124 362X565X124
Weight (without batteries) 4kg 5kg 7kg 8kg
Weight (with batteries) 5.8kg 6.8kg 9.6kg 12.5kg