Product Description
Features
. Universal AC input/Full range
. Protections: Short circuit / Overload / Over voltage
. Cooling by free air convection
. Can be installed on DIN rail TS-35/7.5 or 15
. NEC class 2 / LPS compliant (24V, 48V only)
. LED indicator for power on
. DC OK relay contact
. No load power consumption<0.75W
. 100% full load burn-in test
Specification:
AC input voltage range: 88-264VAC 120-370DC
AC inrush current: Cold start, 30A at 115VAC, 60A at 230VAC
DC adjustment range: Signal Output0± 20%,
Overload protecton: 105-150%, constant current limiting, auto-recovery
Over voltage protection: 125-150%, rated output voltage.
Setup, rise, hold up time: 100ms, 30ms, 100ms at full load and 230VAC
Withstand voltage: I/P-O/P: 3KVAC, I/P-FG: 1.5KVAC, 1minute
Working temperature: -20-55º C@100% 70º C@ 60% load(5V only -20-45º C@100%, 70º C@50% load)
DC OK signal: Relay contact
DC OK relay contact(40-60W)
Safety standards: UL508, TUVEN60950-1.
EMC standards: EN55022D class B, EN61000-3-2, EN61000-4-2, 3, 4, 5, 6, 8, 11, EN61204-3
Connection: I/P: 3 poles, O/P: 6 poles screw DIN terminal
Dimension: (L*W*H)mm 40*90*100