Model NO.
TRZ-C01/F-4828.5-152/PA31A01/SY-0.5
It is installed at the position of generator cooler cold & hot air, core cold & hot hydrogen and collecting ring brush carrier, cannot be easily replaced. Long-term stability and service life is particularly critical.
Element: Thin film element can ensure relatively low natural temperature rise. Single element and double element is available.
Insulation shell: Level F and H insulation material is provided.
Lead: High-temperature resistance and corrosion resistant fluoroplastics; fluoroplastic sheathed control cable
Application of 0.60 million generator cooler heating & cooling air and nitrogen and collecting ring brush carrier:
It is used for temperature measurement for steam turbine generator cooler, heating & cooling air and nitrogen and for collecting ring brush carrier, is a monitoring means to ensure safe and reliable operation of generator winding.
Customization of 0.60 million generator cooler heating & cooling air and nitrogen and collecting ring brush carrier:
Thermal response time less than 5s;
Integrated molding, high strength;
Rear withstanding 4,000V, silicon resin glass fiber protective casing
Technical parameters of 0.60 million generator cooler heating & cooling air and nitrogen and collecting ring brush carrier:
Product mode:TRZ-C01/F-4828.5-152/PA31A01/SY-0.5
Index No.: Pt100
Temperature range: 0ºC~180ºC, allowance Level B;
Wire system : Two-wire system
Thermal response :less than 5s;
Insulation resistance: 500V tramegger, insulation resistance under normal temperature larger than 100MΩ;
Under thermal state 180ºC, larger than 10MΩ (type test);
Withstand voltage 2500VAC , in good condition after duration of 1min;
Impact resistance: the element is able to sustain three impact tests freely falling from height of 1.5m and dropping onto cement ground.