Product Description
Product Details >>
KEYPOWER GENERATOR TESTER SPECIFICATIONS |
Measurement | Range | Accuracy | Resolution | Overload |
Voltage (V) | 10.0~500.0V | ± (0.4% reading+0.1%range) | 0.1V | 600V |
Current (A) | 0.030~5.000A | ± (0.4% reading+0.1%range) | 0.001A | 6A |
Power | According to volt range & current range | Power factor =1.0 | <200W 0.1W | |
± (0.4% reading+0.1% range) | ≥200W 1W |
Power factor =0.5 | ≥2kW 10W |
± (0.8% reading+0.2% range) | |
Power Factor | 0.20~1.00 | ±0.02 | 0.001 | |
Frequency | 45~65Hz | ±0.2Hz | 0.01Hz | |
|
Running Time | 99h59m | ±2min/hour | 1 minute | |
Energy (kWh) | 99999kWh | Power factor= 1.0 | 0.001kwh | |
± (0.4% reading+0.1% range) |
Power factor=0.5 |
± (0.8% reading+0.2% range) |
Harmonic Analysis (%) | 2-50 times and total harmonic | | | |
Models You Can Choose |
Model | Testing capacity | Type of load | Duty | Cooling system | Phase | Rated Testing Voltage | Rated Frequency | Dimensions (L*W*H) (mm) | Weight (kg) |
KPLB-100 | 0 - 100 kw | Resistive or Reactive, PF = 1.0 or 0.8 | Continuous | Industrial grade axial fan | Available at both single and three phase | 110-480 VAC | 50/60 Hz | 960*960*1400 | 320 |
KPLB-200 | 0 - 200 kw | 1300*1200*1570 | 500 |
KPLB-300 | 0 - 300 kw | 1600*1200*1700 | 900 |
KPLB-400 | 0 - 400 kw | 1600*1400*1700 | 1000 |
KPLB-500 | 0 - 500 kw | 2100*1560*1700 | 1200 |
KPLB-600 | 0 - 600 kw | 2100*1560*1700 | 1300 |
KPLB-700 | 0 - 700 kw | 2100*1560*1800 | 1400 |
KPLB-800 | 0 - 800 kw | 2100*1660*1900 | 1600 |
KPLB-1000 | 0 - 1000 kw | 2200*1900*2150 | 2000 |
KPLB-2000 | 0 - 2000 kw | 20 ft container | 6000 |
KPLB-5000 | 0 - 5000 kw | 40HC container | 16000 |
Specifications
100-2000KW Load Bank for Generator Load Test:
1.Premium components
2.Durable and reliable
3.Easy to transport
Load bank is a simulating load test equipment used for generators, UPS,
battery banks etc power systems load test.
1. Resistive type of load, PF = 1.0. Stainless steel sheathed elements manufactured from high grade magnesium oxide.
2. Rated testing voltage: AC 3P4W, 110-480V 50/60 Hz.
3. Cooling mode: Forced air-cooled, fans mounted on the side of the load bank blow horizontally. Testing power or external utility power supply for fans.
4. Working mode: Load step control
Total testing capacity ranges from 0kw to the max consisting of 10kw, 20kw, 50kw, 100kw load setting switches plus a 0-10kw fine-tuning knob. From 0kw to the max, any load combination is achievable. Load step resolution is 10kw.
5. Load bank features world-famous components to ensure reliable performance and longer service life including:
Siemens switches, knobs and indicators.
OMRON intermediate relays.
PHOENIX terminal blocks.
6. Parameter measuring accuracy grade: 0.3
7. Load control accuracy: ±; 5%.
8. Load bank protections: Over heating protection, cooling fans failure protection and over load protection with alarm.
9. Control mode: Two control modes available:
A)Local manual control;
B)Optional: Manual control via a remote control panel (max control distance is 30m).
10. Parameter display and measurement:
Control panel contains a LOVATO Multifunction Electricity Meter displaying voltage, current, load power, reactive power, apparent power, power factor, frequency etc.
(Optional: A professional generator tester displays and measures all sorts of steady, dynamic parameters as well as harmonic wave, can be connected to a PC for data recording and test report printing). "
11. Operating environment:
Altitude: &le; 3000m above sea level. Ambient temp: -10~+50 ºC
Relative humidity: &le; 80% ventilated environment without explosive or corrosive dust. Not allowed to use in rainy outdoor environment.
Any question, please contact me directly.
Address:
Rm. 1013, Bafang Mansion, No. 24 Dongda Road, Gulou District, Fuzhou City, Fujian Province, Fuzhou, Fujian, China
Business Type:
Manufacturer/Factory
Business Range:
Industrial Equipment & Components, Instruments & Meters, Manufacturing & Processing Machinery
Management System Certification:
ISO 9001, ISO 14001
Company Introduction:
Supply fuel filter, oil fulter, air filter, oil-water filter. And 5 - 3000 kw diesel generator set, 100 - 2500 kw load banks.