Introduction(1)Basic Functions
- Sensor suitable:DN3~DN2800
- Range of rate:0.01m/s~12m/s
- Accuracy:Level 0.25
- Low-frequency square wave or High-frequency Excitation
Excitation frequency:3.125Hz,6.25Hz,12.5Hz,25Hz - Excitation Current:100mA ~500mA,Default 160mA or 250mA
- Language:Display in Chinese,English and other customized
- Power:86V~265VAC,18V~36VDC
- Output Signal:1.4-20mA 2.Pulse 3.Frequency 4.High and Low Alarm or Relay
- Communication:Modbus(RS485),HART,GPRS
- Display:Instantaneous flow rate,Velocity,Positive accumulation,Negative accumulation,Net accumulation,Signal voltage value
(2)Working Condition
Temperature:-10~60ºCHumidity:5%~95%Power:86V~265VAC,18V~36VDC Power Consumption<15W(With the sensor)(3)Basic Format
A.Circular shellB.Square shell(4)Sensor Matching Requirements
The signal sensitivity will be 150 microV to 200 microV for 1 m/sThe excitation current can be customized from 100mA to 500mA.The resistance for each excitation current:125mA is 100-120 Ohms160 mA is 60-100 Ohms250 mA is 40-60 Ohms.(5)The Machine Accuracy
0.25%,0.5%(6)Analog Current Output
Load resistance:0-500ΩThe basic error:0.1%±10μA(7)Digital Frequency Output
Range:1~5000HzOutput electrical isolation:Optoelectronic isolation.Isolation voltage:More than 1000 VDC.Frequency output driver:Field effect tube output,Max 36 VDC power supply,Max 250 mA load current.(8)Digital Pulse Output
The output pulse equivalent is set by client.The output pulse width:50msOutput electrical isolation:Optoelectronic isolation.Isolation voltage:More than 1000 VDC.Pulse output driver:Field effect tube output,Max 36 VDC power supply,Max 250 mA load current.(9)High and Low Alarm Output
Alarm output:H -High alarm, L -Low alarmOutput electrical isolation:Optoelectronic isolation.Isolation voltage:More than 1000 VDC.Alarm output driver: Darlington pipe output,Max 36 VDC power supply,Max 250 mA load current.(10)Electrical Isolation
Insulation voltage between Analog input and Analog output:not less than 500V;Insulation voltage between Analog input and Alarm power:not less than 500V;Insulation voltage between Analog input and AC power:not less than 500V;Insulation voltage between Analog output and AC power:not less than 500V;Insulation voltage between Analog output and Ground:not less than 500V;Insulation voltage between Pulse output and AC power:not less than 500V;Insulation voltage between Pulse output and Ground:not less than 500V;Insulation voltage between Alarm output and AC power:not less than 500V;Insulation voltage between Alarm output and Ground:not less than 500V.
Address:
169 Luojin Road, Shanghai, China
Business Type:
Manufacturer/Factory
Business Range:
Industrial Equipment & Components, Instruments & Meters, Manufacturing & Processing Machinery
Company Introduction:
Flosonic Automation Co., Ltd is dedicated to the research and development and production of the flowmeter converter. Our products have independent intellectual property rights, we always adhere to the arduous struggle, innovation, entrepreneurial spirit. We are having a long-term cooperation with the University of Science and Technology of China, Hefei University of Technology, strengthening the exchange and cooperation with South Korea FNS Plus company, constantly develop new functions, new technologies and new products to satisfy and guide new demand and new development of customer and market′s.
Our products of flowmeter converter are selling to Taiwan, over 20 provinces of China, and South Korea, India, Russia, Italy and other countries and regions, and widely used in petroleum, chemical, metallurgy, electric power, water treatment, paper making, food, medicine and other fields.