Basic Info.
Installation
Direct Connected
Usage
Multi-Functional Energy Meter, Watt-Hour Meter, Meter for Industry and Home Use, Standard Electric Energy Meter, Reactive Energy Meter, Multi-rate Watt-hour Meters, Maximum Demand Meter
Electric Equipment
2 Phase Meter
Power Meter Connection
Terminal
Measured Signal
Pulse Peak
Certification
RoHS, ISO, CE
Transport Package
Paper Box
Product Description
1. Introduction
This is a two phase three wires meter with CIU through twisted pair which complies with STS prepaid standard. Built-in relay which can trip when over load, balance run out, tamper happen and so on. Opening the terminal cover will have tamper indication.
- Features and Technical Parameters
2.1 Features
•First paid, then USE electricity
•Protection Degree IP54 with ultrasonic bwtween base and cover.
•The meter communicate with CIU through twisted pair. Screw connector between meter with extra keypad
•Keypad with 20number token to charge, no need IC card
•Keypad lifetime is more than 25000 times (test in third LAB)
•Events record for terminal cover opening, included Date and Time.
•Low balance credit alarm, emergency alarm
•LCD display for kinds of values: remain credit, total kWh, constant voltage, constant current\ and so on.
•LCD can display pages by press the button
•Display kinds different info through short code
•Internal 120A relay, can power off the meter when no credit.
•Over load protection
•Upper cover and terminal cover tamper protection
•support IR communication according to IEC1107 with bate rate9600.
2.2 Technical Parameters
Voltage: 2*127/220V
Current: 2*10(100)A
Accuracy class: 1.0
Standard: IEC 62052-11 testing, IEC 62053-21, IEC 62053-22IEC
Frequency: 60Hz
Impulse constant: 1000imp/kWh
Display: LCD 6+2
Power consumption: ≤10VA ≤1W
Starting current: 0.4%Ib
Temperature range: -25~70ºC
Average humidity value of year: 75%
value: 95%
Communication: IR IEC1107
- Description
Description of CIU
A relay state indication
B credit state indication
C 3*4 keypad
D LCD
E IR communication interface
Material:
Meter base ABS
Meter cover ABS
- Connection Diagram
4.1 Meter diagram
5. Dimensions
5.1 Meter size
5.2 CIU size
- Software
6.1.1 meter LCD Screen
6.1.2CIU LCD Screen
6.1.2.1 Display content of CIU
Balance Credit 0000000.00 kWh
Time
Date
6.1.3 Display mode
LCD display support turning pages through button.
6.1.4 Short Code information
a. Set Alarm Credit: input 456-XXXXX, and then enter return key. XX is alarm credit (kWh),allowed range 10-99999l.
b. Alarm Buzzer Interval: input 123XXX, and then enter return key. XXX is interval (minute),allowed range 0-999.
c. Clear tampering state: input 12345, and tehn enter return key.
6.1.5 Short Code query
Short code information:
Code | Description | Code | Description |
0 | LCD test(full page display) | 42 | Phase B voltage |
1 | Relay test | 43 | NULL |
2 | Alarm test and LCD test(full page display) | 44 | Phase A current |
3 | Total kWh | 45 | Phase B current |
4 | Password modify number&type | 46 | NULL |
5 | Tariff list | 47 | Phase A active power |
6 | NULL | 48 | Phase B active power |
7 | Power | 49 | NULL |
8 | Tampering state | 50 | SGC |
9 | Total power of constant phase sum | 51 | The times of relay disconnect |
10 | Meter software version | 52 | The times of meter kWh clear |
11-13 | NULL | 53-74 | NULL |
14-18 | Token record for last 5 times | 75 | Meter hardware version |
19 | Meter serial number | 76 | Meter constant |
20-22 | NULL | 77 | Low credit alarm threshold |
23 | Remain kWh | 78 | Alarm period (S) |
24 | Total charged kWh | 79 | NULL |
25 | Constant frequency | 80 | Over load times |
26 | High voltage threshold | 81 | Power off times |
27 | Low voltage threshold | 82 | Upper cover open times |
28-29 | NULL | 83 | Terminal cover open times |
30-34 | Token record for last 5 times | 84-97 | NULL |
35 | Token times | 98 | date |
36 | Technical Token times | 99 | time |
37-39 | Technical token record for last 3 times | | |
40 | Recieved Token times | | |
41 | Phase A voltage | | |
6.2.5 Balance credit alarm
The meter has the function of class1 balance credit alarm. Alarm threshold could be set through short code or communication. When the remain kWh is less than the threshold, the red LED will be flashing and the buzzer will alarm. If the kWh usage up, the relay will open and the LED will keeping red.
Address:
No. 320 Tongsheng Rd., Tongxiang, Jiaxing, Zhejiang, China
Business Type:
Manufacturer/Factory
Business Range:
Industrial Equipment & Components, Instruments & Meters
Management System Certification:
ISO 9001, ISO 9000
Company Introduction:
Zhejiang Yongtailong Electronic co., Ltd. Established in 2000. Through these years efforts, YTL become the global famous manufacturer in energy metering industry. YTL have a professional development team, leads the product concept and designs of the market all the time. We are capable of supplying a variety of meters, We are also expert in designing & providing for ourselves the meter main components such as Meter Shunt, Current Transformer, Potential Transformer etc...YTL is devoted to developing and designing high performance low price products and providing service for electric measurement, creating value for customers. Especially in electric measurement and energy-saving field, YTL′s products export to more than 50 countries over the world, and cover various of electric and energy-saving markets.