Basic Info.
Transport Package
Inner Box, Then in Carton
Product Description
1 General GW1-35 Outdoor high voltage separation relationship outdoor installation general purpose isolating switch. Forthree-phase alternating current 50Hz. Rated voltage 12KV AND 35KV and below the power system. The circuit is switched on when there is a voltage without a negative voltage.. The product is in line with the GB1985 "AC high voltage isolation switch and grounding switch". DL486 order "technical conditions for AC high voltage isolating switch,The national standard DL/T593 "high voltage isolation switch equipment common order technical conditions" and the power industry standard. 2 Using environmental conditions.2.1 altitude 4000M.2.2 ambient temperature is -25 degrees C to +40.2.3 wind pressure is not more than 700Pa.2.4 ice thickness is not more than 1mm.2.5 earthquake intensity is not more than 8 degrees.2.6 the installation site should have no regular violent vibration and flammable. Effect of explosive material and chemical corrosion.4 Model specifications and technical parametersSerial number | Project | Model specification |
630A | 630 A D | 3150A | 3150A D | 4000A | 4000A D |
1 | Rated voltage(kV) | 35 | 35 | 35 | 35 | 35 | 35 |
2 | Maximum operating voltage(kV) | 40.5 | 40.5 | 40.5 | 40.5 | 40.5 | 40.5 |
3 | Rated current(A) | 630 | 630 | 3150 | 3150 | 4000 | 4000 |
4 | 4S short-time withstand current(kA) | 25 | 25 | 31.5 | 31.5 | 31.5 | 31.5 |
5 | Rated peak withstand current(kA) | 63 | 63 | 80 | 80 | 80 | 80 |
6 | 1minEffective value of power frequency withstand voltage | On the ground | 42 | 42 | 42 | 42 | 42 | 42 |
Fracture | 48 | 48 | 48 | 48 | 48 | 48 |
5 Structure principle5.1GW1 - 35 switch outline and installation dimensions are shown in Figure 2.GW1 - 35 for single phase structure. Each phase consists of a chassis, the main knife (ground knife), movable contact head, static contact head, shaft, rod insulators. Three-phase through a connecting pipe is connected, the operation shaft with rod insulators to drive the main knife switch, touch knife with trough outline form, increased mechanical strength and heat dissipation area.5.2 GW1-35D -switch is a kind of switch on the GW1 - 35 to add a ground knife.Equipped with CS6-2 operating mechanism after the, can achieve the main knife switch, knife cannot contract; knife switch, the surgeon can not closing the anti error interlocking requirements.5.3 GW1 - 35 switch with CS6-2 mechanism (see Figure 1).6 Installation and adjustment6.1 GW1 - 35 in the installation site for three - phase connection and the operation of the motivation structure. Installation diagram see Figure 3. The 2 switch based 10 channel as channel and switch bottom mounting frame.Vertical arrangement of frame. To adjust in the following order.6.2 The switch is arranged on the foundation (the main contact cutter and the grounding knife in the closing state) adjust three-phase coaxial switch. 3/4 water gas pipe three switch welding connection.Then Switch fixed.6.3 The handle of the mechanism is arranged in the same position with the switch of the switch. The crank arm is welded to the water gas pipe. Attention should be paid to the welding angle and length of the crank arm. GW1 - 35 switch principal axis welding long crank arm L = 120,W1 - 35 switch,The main knife shaft welding arm L = 120mm, grounding knife shaft welding arm L = 120mm. according to the size of welding rod installation.6.4 Connecting the switch and the actuating mechanism with the connecting rod. Three-phase synchronization inching switch, the three phase is less than or equal to 3mm.6.5 Switch installation adjustment is completed. Operation 20 times to check parts is loose, three-phase synchronization changes, the earthing switch is closing in place, operating mechanism can reach the designated position and lock.6.6 After installation and adjustment, according to the following acceptance of the project. Serial numbe | Acceptance content | technical requirement |
1 | Appearance | Testing | Rust proof. The switch name brand is correct, the position is correct. The fastening part of the fastener without loosening, and ensure the verticality and shaft coaxial switch. |
2 | Spring pressure | 630A | 431±39N |
1250A 3150A | 441±44 |
3 | The main knife fracture distance | ≥360mm |
4 | Ground knife fracture distance (on the ground) | ≥360mm |
5 | The main switch three phase | ≤5mm |
6 | Operating torque | The main knife | ≤300N·M |
The grounding knife | ≤300N·M |
7 | The surgeon and the knife body chain | Don't switch on the main knife knife switch, knife knife not closing closing. |
8 | Switching operations | The operation is flexible, convenient and accurate. Check pin down hole correctly. The main and the ground knife can be divided into place. |
7 Operation and maintenance 7.1 Before putting into operation, the contact parts of the conductor should be in good contact with each other. Switch and bus connection should be reliable. The moving parts should be flexible. 7. 2 Operation: the switch must be cut off before the line can be operated. 7.3 Switch shall be carried out for 12 times a year, and the following items should be paid attention to during the overhaul: 7.3.1 Check the stability of the structure and the connection is reliable. 7.3.2 Maintenance of conductor contact surface is in contact with the surface coated with neutral vaseline. 7.3.3 Replace damaged parts.
Address:
Yueqing Economic Development Zone, Wenzhou, Zhejiang, China
Business Type:
Manufacturer/Factory
Business Range:
Electrical & Electronics
Management System Certification:
ISO 9001
Company Introduction:
We, Chage E& M Equipment Co., Ltd., which is proffessional manufacturer and distributor of Medium & High Voltage, Outdoor & Indoor Electric Power Equipments in China.
And our products are sold to domestic markets widely, furthermore, are exported to many countries worldwide.
Our company lies in Lucheng District, Wenzhou and her producing factory lies in Zhejiang Yueqing.
We would like supply customers with diversified and efficient electric power management solutions.