1.Product descriptions
JCZ8 series AC high voltage vacuum contactor is suitable for AC 50~60Hz,main circuit rated voltage 12kV,rated current from 160A to 1000A power network system for remote making and breaking and frequent starting and controlling AC motors, transformers,capacitor banks and other occasions .
2.The use of the environment conditions
2.1.Ambient temperature:-25 ºC ~ +40 ºC.
2.2.Installation site altitude does not exceed 2000m.
2.3.The relative humidity of the air,the wettest month average monthly maximum relative humidity of 90%,monthly average minimum temperature of 25ºC,and taking into account the cream of temperature changes on the surface of the product.
2.4.Environment:anhydrous invasion,non-corrosive and flammable gas and excessive vibration occasions.
3.Product Specification
Rated voltage:12kV, rated current:160A,250A ,400A ,630A,800A and1000A.
4.Working principle
The electromagnetic holding type:
Three-phase vacuum tube through the insulator and conductive rod lever,the contact connected to the cantilever springs,cantilevers and armature are fixed on the shaft.
During closing,solenoid armature coil snap-keep,inward movement,the upward motion of the cantilever,vacuum tube through the contact spring contact is closed and provides a contact pressure to ensure reliable close.When switch open,the electromagnetic coil power lose suction opening,moving the armature in the sub-gate under the action of the spring,the outward movement of cantilever downward movement, downward movement by pulling
the lever,pull the insulator,moving conducting rod,contact separation requirements distance to achieve a reliable sub-gate.
Due to electromagnetic systems require larger power in armature snap and snap in place maintain power greatly reduced,in order to save electricity,synchronized by the auxiliary switch snap,maintain conversion.Auxiliary switch also provides user external control you need.With DC excitation of electromagnetic system,auto-control circuits with rectifiers,so users can be controlled directly from the AC power.As the vacuum switch main contacts close/open is conducted in vacuum,which has a good breaking characteristics,long life,safe and reliable.
5.Technical parameter
5.1.Main technical characteristics Technical parameter | Value |
Main circuit rated voltage (kV) | 12 | 12 | 12 |
Main circuit rated current (A) | 160/250 | 400 | 630 |
Main circuit making capacity (A/100times) | 2500 | 4000 | 6300 |
Main circuit break-make ability (A/25times) | 2000 | 3200 | 5000 |
Ultimate breaking capacity(A/3times) | 4000 | 4500 | 6300 |
Mechanical life(Times) | 100 0000 | 100 0000 | 100 0000 |
Electricity life AC3(Times) | 25 0000 | 25 0000 | 25 0000 |
Electricity life AC4(Times) | 100000 | 100000 | 100000 |
Lightning impulse withstand voltage(kV) | 75 | 75 | 75 |
Power-frequency withstand voltage of the main circuit(fracture)(kV) | 42 | 42 | 42 |
Phase-phase/phase-ground power frequency withstand voltage(kV) | 42 | 42 | 42 |
Power-frequency withstand voltage of the control circuit (kV) | 2.5 | 2.5 | 2.5 |
Rated operating frequency (Times/h) | 300 | 300 | 300 |
Terminal pressure(N) | >100 | >150 | >150 |
Clearance between open contacts (mm) | 6±0.5 | 6±0.5 | 6±0.5 |
Overtravel(mm) | 1.5±0.5 | 1.5±0.5 | 1.5±0.5 |
Main circuit contact resistance( μΩ ) | ≤200 | ≤200 | ≤200 |
Technical parameter | Value |
Main circuit rated voltage (kV) | 12 | 12 |
Main circuit rated current (A) | 800 | 1000 |
Main circuit making capacity (A/100times) | 8000 | 10000 |
Main circuit break-make ability (A/25times) | 6300 | 8000 |
Ultimate breaking capacity(A/3times) | 6300 | 8000 |
Mechanical life(Times) | 100 0000 | 100 0000 |
Electricity life AC3(Times) | 25 0000 | 25 0000 |
Electricity life AC4(Times) | 100000 | 100000 |
Lightning impulse withstand voltage(kV) | 75 | 75 |
Power-frequency withstand voltage for the main circuit (fracture)(kV) | 42 | 42 |
Phase-phase/phase-ground power frequency withstand voltage(kV) | 42 | 42 |
Power-frequency withstand voltage for the control circuit (kV) | 2.5 | 2.5 |
Rated operating frequency (Times/h) | 300 | 300 |
Terminal pressure(N) | >150 | >150 |
Clearance between open contacts (mm) | 6±0.5 | 6±0.5 |
Overtravel(mm) | 1.5±0.5 | 1.5±0.5 |
Main circuit contact resistance( μΩ ) | ≤200 | ≤200 |
5.2.Number of poles:3
5.3.Control voltage:AC/DC 110V/220V/380V,or could be customized which is based on the client's requirements.
5.4.Auxiliary switch contact circuit conventional heating current is 5A.
5.5.Rated working system:intermittent long-term work system,repeated short-term work system(rated power on rate of 40%).