Basic Info.
Type
Basic Diesel Generator
Installation Method
Portable
Cooling Method
Air Cooled
Output Type
AC Three Phase
Product Description
Functions & Features
Test three-phase voltage, current, active power, reactive power, apparent power, power factor, frequency, running time, energies of generators and UPS.
It has harmonic analysis of 2-50 orders of harmonic content and the total harmonic content for voltage or current.
Set/adjust discharging power according to performance parameters and detection requirements
Set discharging time, timing to automatic shut-off load, discharge off and alarm operator
Set over/under voltage protection threshold value, it can shut off load, terminate discharging and alarm user automatically.
Large LCD screen, friendly interface. English menu and easy operation.
Parallel operation function to carry out multi sets load operation by RS 485 communication
Built-in storage save 30 groups of test data, which can be viewed, deleted and export into SD card.
Start/stop discharging control by Serial port, and detect data real time operation etc.; The storage data can be uploaded to PC by serial port or SD card, and the upper computer's software can analyze data and pattern and print report etc.
Overheating and over current protection function, it can turn off load, terminate discharging and alarm automatically when over temperature and over current.
Set at most 5 groups power, load process automatically according to the setting power and operation time after being turned on.
Technical Specifications
Mode | JET-ACO 380/02 | JET-ACO 380/04 | JET-ACO 380/10 |
Load voltage | Three-phase AC380V, Single-phase AC220V |
Operating power | Stand-alone: Max 20KW (Three-phase 380V) Max 6KW (Singly-phase 220V) | Stand-alone: Max 40KW (Three-phase 380V) Max 13KW (Singly-phase 220V) | Stand-alone: Max 100KW (Three-phase 380V) Max 30KW (Singly-phase 220V) |
Cooling mode | FCT (Fan control Temperature) |
Communication Mode | RS232, RS485 and SD card |
Display mode | 8-inch TFT |
Voltage measurement range | AC 0~450V, Display Resolution: 0.1V, Precision: ±0.5% |
Current measurement range | AC 0~100A, Display Resolution: 0.1A, Precision: ±0.5% | AC 0~150A, Display Resolution: 0.1A, Precision: ±0.5% | AC 0~300A, Display Resolution: 0.1A, Precision: ±0.5% |
Frequency measurement range | 40~60 Hz, Display Resolution: 0.01Hz, Precision: ±0.2% |
Power measurement range | 0~20 KVA, Display Resolution: 0.1KVA, Precision: ±1% | 0~40 KVA, Display Resolution: 0.1KVA, Precision: ±1% | 0~100 KVA, Display Resolution: 0.1KVA, Precision: ±1% |
Power factor measurement range | 0.001~1.000, Display Resolution: 0.001, Precision: ±0.5% |
Discharging Time | (0~19 hours and 59 minutes) adjustable continuously |
Quantity of Parallel operation | 1~99 sets |
Recording Period | 6~999 Seconds |
Temperature measurement range | -20~100ºC,Display resolution: 1ºC, precision:±1ºC |
Insulating strength | Input≥AC1500V, Output≥AC500V |
Working environment | Working Temperature: (-20~55)ºC, Storage Temperature: (-45~75)ºC Relative humidity: 90%(40±2ºC) Atmospheric pressure: (70~106) KPa |
Working power supply | Single-phase AC220V±10, 50Hz |
MTTF | ≥50000h |
Dimensions(mm) | 420×500×750mm | 680×600×900mm | 680×600×900mm |
Weight | 30kg | 50kg | 70kg |
| | | | | | | |
Mode | JET-ACO 380/20 |
Load voltage | Three-phase AC380V, Single-phase AC220V |
Operating power | Stand-alone: Max 200KW (Three-phase 380V) Max 66KW (Singly-phase 220V) |
Cooling mode | FCT (Fan control Temperature) |
Communication Mode | RS232, RS485 and SD card |
Display mode | 8-inch TFT |
Voltage measurement range | AC 0~450V, Display Resolution: 0.1V, Precision: ±0.5% |
Current measurement range | AC 0~400A, Display Resolution: 0.1A, Precision: ±0.5% |
Frequency measurement range | 40~60 Hz, Display Resolution: 0.01Hz, Precision: ±0.2% |
Power measurement range | 0~200 KVA, Display Resolution: 0.1KVA, Precision: ±1% |
Power factor measurement range | 0.001~1.000, Display Resolution: 0.001, Precision: ±0.5% |
Discharging Time | (0~19 hours and 59 minutes) adjustable continuously |
Quantity of Parallel operation | 1~99 sets |
Recording Period | 6~999 Seconds |
Temperature measurement range | -20~100ºC,Display resolution: 1ºC, precision:±1ºC |
Insulating strength | Input≥AC1500V Output≥AC500V |
Working environment | Working Temperature: (-20~55)ºC, Storage Temperature: (-45~75)ºC Relative humidity: 90%(40±2ºC) Atmospheric pressure: (70~106) KPa |
Working power supply | Single-phase AC220V±10, 50Hz |
MTTF | ≥50000h |
Dimensions(mm) | 1300×600×900mm |
Weight | 150kg |
Mode | JET-ACO 380/50 |
Load voltage | Three-phase AC380V, Single-phase AC220V |
Operating power | Stand-alone: Max 500KW (Three-phase 380V) Max 160KW (Singly-phase 220V) |
Cooling mode | FCT (Fan control Temperature) |
Communication Mode | RS232, RS485 and SD card |
Display mode | 8-inch TFT |
Voltage measurement range | AC 0~450V, Display Resolution: 0.1V, Precision: ±0.5% |
Current measurement range | AC 0~400A, Display Resolution: 0.1A, Precision: ±0.5% |
Frequency measurement range | 40~60 Hz, Display Resolution: 0.01Hz, Precision: ±0.2% |
Power measurement range | 0~500 KVA, Display Resolution: 0.1KVA, Precision: ±1% |
Power factor measurement range | 0.001~1.000, Display Resolution: 0.001, Precision: ±0.5% |
Discharging Time | (0~19 hours and 59 minutes) adjustable continuously |
Quantity of Parallel operation | 1~99 sets |
Recording Period | 6~999 Seconds |
Temperature measurement range | -20~100ºC,Display resolution: 1ºC, precision:±1ºC |
Insulating strength | Input≥AC1500V Output≥AC500V |
Working environment | Working Temperature: (-20~55)ºC, Storage Temperature: (-45~75)ºC Relative humidity: 90%(40±2ºC) Atmospheric pressure: (70~106) KPa |
Working power supply | Single-phase AC220V±10, 50Hz |
MTTF | ≥50000h |
Dimensions(mm) | 1600×1200×1650mm |
Weight | 350kg |
Address:
1001 of Block a, National Digital Publishing Base, 996 Tiangu Qi Road, Xhtz, Xi′an, Shaanxi, China
Business Type:
Manufacturer/Factory, Trading Company
Business Range:
Instruments & Meters
Company Introduction: